Page 10Installation
Restore Defaults
Range: Yes, No / Default: No
Restores all settings to factory defaults.
Press Yes to restore defaults.
Press No to exit and not restore defaults.
Relay Status
Display the status (on/off) of the thermostat output relays
Setting Range Default
Display Lock Y or N N Locks out front buttons
Service Mode Submenu
Test Mode Y or N N Reduces delays for testing
System Settings Submenu
Mechanical Settings Submenu
Sys Type Std or HP Std
Fan Type Gas or Elec Gas
C/O Type w/Heat or w/Cool w/Cool
2nd Stage Heat Y or N N
Aux Heat Y or N Y
2nd Stage Cool Y or N N
H/C Delta 3 – 15 deg 3
Heat Delta Stage 1 On 1 – 8 1
Heat Delta Stage 1 Off 0 – 8 0
Heat Delta Stage 2 On 1 – 8 2
Heat Delta Stage 2 Off 0 – 8 0
Heat Delta Stage 3 On 1 – 8 3
Heat Delta Stage 3 Off 0 – 8 0
Cool Delta Stage 1 On 1 – 8 1
Cool Delta Stage 1 Off 0 – 8 0
Cool Delta Stage 2 On 1 – 8 2
Cool Delta Stage 2 Off 0 – 8 0
Max Heat SP 40-109F (4-42C) 90F
Min Cool SP 44-113F (6-45C) 60F
Min Run Time 1-9 min 3
Min Off Time 1-9 min 5
Temp Response 1-6 2
Fan Cycler Submenu
Fan Cycler ON time 0 – 120 min 0 0 = Fan Cycler OFF
Fan Cycler Off Time 10 – 120 min 10
Restore Defaults Yes or No No Exit = no
Installer Settings Summary